Abstract:The main circuit structure, operation mode, grounding electrode and its function of Zhangbei flexible DC transmission project are introduced, and the importance of grounding resistance as grounding electrode is described. Aiming at the possible faults of grounding electrode, the adopted real time monitoring methods are studied and analyzed. The differences between voltage and current method and injection method are compared, and the reasons and advantages using injection method for Zhangbei flexible DC project are also explained. The selection basis of injection signal frequency is analyzed. According to the system characteristics and parameters of Zhangbei flexible DC project, the primary equipment and the structure of monitoring circuit are selected to meet the injection principle. Through the theoretical analysis and system simulation test, the influence of wave trap coil or not on main system is verified. Finally, the technical scheme of on line monitoring of grounding electrode in Zhangbei flexible DC project is determined.