Abstract:When discharge or overheating fault occurs in oil paper insulated bushing, the internal insulation oil and insulation paper will be decomposed to produce characteristic gas, and the internal pressure will increase correspondingly with the increase of gas, so that the monitoring and warning of defects can be realized by monitoring the internal pressure of bushing. However, the changes in ambient temperature and load current will lead to the changes of temperature inside the bushing, which will lead to the changes in internal pressure, thus bringing disturbance to the early warning using pressure monitoring. In order to eliminate the disturbance of temperature on pressure warning, the law of the influence of temperature on internal pressure is studied, and the method of common mode suppression to eliminate the influence of temperature is proposed. The results show that the proposed method can effectively eliminate the influence of temperature on pressure monitoring of bushing.