Abstract:In recent years, a large number of electrified railways have been connected to Xinjiang power grid, resulting in prominent power quality problems in weak connection areas of Xinjiang power grid. The influencing factors of three-phase unbalance caused by the connection of Geermu-Kuerle Railway to Xinjiang Bazhou regional power grid is analyzed. Firstly, according to the concept and expression of threephase voltage unbalance, the negative sequence three-phase unbalance of electrified railway is analyzed and calculated, and the influencing factors of threephase unbalance are obtained. Secondly, based on the comprehensive analysis software system of electric power analysis and electric power management (hereinarfter abbreviated as ETAP), a typical simulation model of the connection of Geermu-Kuerle Railway to Xinjiang power grid is built to verify the influencing factors of three-phase unbalance of the connection of electrified railway to the power grid. Finally, the influence of threephase unbalance caused by negative sequence current and negative sequence voltage based on the measured data on the power system and users is analyzed, and ETAP software is used to verify the effectiveness of improvement measures for three-phase voltage unbalance from the railway side and the grid side.