Abstract:The remote control operation regulations of isolating switch and the relationship of anti-isoperation locking are analyzed, the abnormal operation situation is counted, and a practical abnormal operation process is proposed. Aiming at an abnormal closing failure of GW55-26DⅡ isolating switch during the switching operation of 110 kV reactor interval at the low voltage side of main transformer in extra high voltage(UHV) substation, through the analysis on the operation control circuit diagram and working principle, and combined with the arrangement of cable wiring of field devices and the analysis on the relationship of electric locking of isolating switch, the reasons for the isolating switch to refuse to close is determined and the fault is eliminated. Finally, the targeted improvement measures are provided, which will benefit the following maintenance in substations.