Abstract:The low-requency load shedding function integrated in line protection device is of great significance and widely used as the last line of defense in power system, but the misoperation of low-requency load shedding function occasionally occurs. In order to improve the power supply reliability of distribution network, the causes of a low-requency load shedding misoperation event are analyzed, in which ferromagnetic resonance is the cause of misoperation. From the perspective of secondary circuit of protection device, it is analyzed that the small PT saturation and calculation error lead to the deviation of phase-o-hase voltage and frequency calculation, which causes the misoperation of low-requency load shedding function. The causes of misoperation are verified by electromagnetic simulation respectively, and the results are consistent with the actual recording of misoperation event. Finally, according to the causes of misoperation, four improvement measures are put forward from improving voltage sampling and optimizing frequency calculation.