Abstract:For promoting the detection sensitivity of ultra high frequency (UHF) signals and anti-nterference ability for transformer partial discharge, the UHF coil sensor with the upper limit detection frequency, that is 480 MHz, is researched, which can detect UHF current signal of partial discharge from the grounding positions of transformer core and clamps. The partial discharge simulated defect is set up in laboratory, and the signal characteristics of suspend potential discharge and insulating surface discharge of transformer are studied, which can help the type identification of signals detected on site. The anti-nterference method for on-ite transformer detection is also researched. On this basis, the on-ite partial discharge diagnosis and location method of transformer based on broadband combined acoustic-lectrical detection is proposed, and it is verified in a 110 kV transformer in which partial discharge defect is detected. So it can help to improve on-ite detection level and diagnosis accuracy of transformer partial discharge.