Abstract:Resonance of multi-inverter grid-connected system is a problem that must be solved in new power grid with high proportion of renewable energy. After analyzing the advantages and disadvantages of the improved active damping, impedance remodeling and active damper, it is considered that the hybrid damping strategy is more in line with the economic needs of the project. Firstly, the design process of hybrid damping parameters of single LCL inverter is introduced. Based on the analysis of resonance mechanism of multi-inverter system, according to the characteristics of hybrid damping coefficient, a parameter design method is proposed to determine the active damping parameters firstly and then the passive damping parameters, and the total harmonic rate and harmonic factor are used to evaluate the grid-connected power quality. Finally, it is verified on the Matlab/Simulink simulation platform. The results show that the hybrid damping parameters designed by the proposed method have a good suppression effect on the system resonance and can adapt well to the change of system impedance.