Abstract:In view of the reality that virtual grounding frequently occurs in turn-adjustable arc suppression coil system, the causes of virtual grounding are studied considering the influence of equipment parameters and structure settings of arc-suppression coil on its compensation algorithm. Based on the theoretical analysis of arc-suppression coil control principle, the actual operation is simulated, the trigger experiment and shift experiment are designed and completed, and then the influence of arc-suppression coil device on the occurrence of virtual grounding is deeply analyzed and verified, and the optimized structure of trigger device of arc-suppression coil after upgrading is proposed. The threshold test scheme is provided for triggering function detection of arc-suppression coil before being put into operation, and the arrangement strategy of parallel operation of multiple arc-suppression coils is considered, which is helpful to ensure that arcsuppression coil can accurately compensate system capacity flow, avoid virtual grounding, and play a certain positive role in reducing grounding misjudgment in power dispatching.