Abstract:Aiming at a complex power grid accident that the reclosing fails due to the power return from motor after a lightning trip-out of 110 kV transmission lines, the impact of power return from motor on 110 kV terminal system is analyzed in detail in the aspect of wave recording, accident appearance, relay protection behaviour and time sequence of breaker action. The reasonable countermeasures and improvement methods are also proposed.