智能变电站二次设备缺陷试验验证方法
DOI:
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM76

基金项目:


Defect Test Verification Method for Secondary Equipment of Smart Substation
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
    摘要:

    为缩短消缺时间、提高消缺效率,智能变电站二次设备的消缺工作通常未深究缺陷产生的根本原因,缺陷处理过程简单、表面,导致缺陷无法彻底消除,使得相同缺陷可能再次发生。因此,为查明缺陷产生的根本原因,将缺陷产生的原因定位到芯片级、原理级,通常需要对缺陷设备开展深层次缺陷查找、分析工作。基于上述原因,对智能变电站二次设备缺陷的验证和试验方法进行了研究,提出了一种缺陷验证和试验技术。

    Abstract:

    In order to shorten the time of defect elimination and improve the efficiency of defect elimination,the defect elimination of secondary equipment in smart substation usually does not go into seriously the root cause of defects. The defect treatment process is simple and superficial,so that the defects cannot be completely eliminated. Therefore,in order to find out the root cause of defects,the cause of defects is located at the chip level and the principle level,and usually a deep defect detection and analysis for defective equipment is needed. Based on the above reasons,the verification and test methods of defects of secondary equipment in smart substation are studied. A defect verification and testing technique is proposed.

    参考文献
    相似文献
    引证文献
引用本文
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2022-04-11
  • 出版日期: