Firstly,the event that UHV reactive power control action leads to DC power runback is introduced. And then,the causes for DC power runback led by manual removal of HP3 filter are analyzed,and the problems existing in control function software of the absolute minimum filter are pointed out. Finally,on the basis of the existing reactive power control function, the hidden dangers in full power operation situation are analyzed,and the feasible solutions are proposed,which can provide a reference for other converter stations in China.
参考文献
相似文献
引证文献
引用本文
孙光宇,任阿阳.特高压换流站手动切除 HP3 滤波器导致功率回降分析[J].四川电力技术,2019,42(6):81-86. Sun Guangyu, Ren Ayang. Analysis of DC Power Runback Caused by Manual Removal of HP3 Filer in UHVDC Converter Station[J]. SICHUAN ELECTRIC POWER TECHNOLOGY,2019,42(6):81-86.