Abstract:The 10 kV overhead lines of Luzhou power station frequently trip out due to lightning overvoltage in thunderstorm season. The reasons of high trip - out rate are analyzed and the potential solutions are discussed. Theory analysis and field application show that substituting the existing MOA with arrester with gaps can effectively reduce the trip - out rate,which can significantly improve the operational reliability of overhead lines.