Abstract:A case is introduced that a single - phase grounding in 35 kV line develops two points ground fault occurred in different phases,which causes a transformer to be cut off. In order to find the fault point and its evolution,the waves of current and voltage recorded in substation when the fault happened are analyzed. The fault range is calculated with the fault current and the known parameters,which improves the efficiency of fault detection and provides some references for fault analysis of the same kind.