Abstract:There are a lot of problems of two-point ground fault occurred in different phases and different lines caused by single-phase ground fault in small current grounding systems. When two-point ground fault occurs in different phases in arc suppression coil grounding system,due to the influence of neutral point current injection,there is a deviation of different fault phases current in the two fault lines,and the protection can not trip accurately. Based on linear superposition principle,the deviation calculation formula and reasons are derived theoretically,and through using over-current protection module and grounding distance protection module,the two grounding fault lines are determined and tripped quickly,which prevents the expansion of fault scope caused by the further insulation breakdown. The simulation of actual grid fault model proves the correctness and reliability of the proposed method,which has certain theoretical and engineering application value.