The behavior of reactor differential protection is analyzed when switching on shunt reactor at the low voltage side of transformer,and it is pointed out that CT transient saturation is the root cause of triggering mal - operation. Applying ratio - brake characteristic and second harmonic blocking can avoid mal - operation to a large extend,however,in the case of small phase current and small brake current,the ratio - brake characteristic cannot play its due function. Furthermore,after CT saturation,second harmonic in differential current is very low,which will cause second - harmonic blocking invalid. A new algorithm is presented to avoid mal - operation caused by CT transient saturation. This algorithm makes use of the ratio of DC and fundamental component to get a correction factor,and then get a corrected differential current. Theory and practice show that there is not any mal - operation of shunt reactor differential relaying since this new algorithm is applied.