Based on the different operation modes of Xinjiang UHV AC/DC hybrid sending grid in 2016,the influence of different failures occurring in ±800kV UHVDC transmission system on the voltage of AC system near the Kumul Prefecture is analyzed through simulation. Different control strategies are adopted according to different failure forms,and the influence of different control strategies on the operating voltage of AC/DC hybrid transmission system is analyzed. The research results are as follow:when DC system failure occurs,in view of different types of failures,DC monopole blocking results in low power surplus and a less influence on system operating stability; Bipolar blocking results in high power surplus which leads to the decrease of AC bus voltage along the line,even the voltage instability and a big influence on AC/DC hybrid transmission system. Commutation failure has a large effect on system transient voltage stability. With the constantly increase of DC power delivered to the outside,no matter DC bipolar blocking failure or the commutation failure,they all will lead to more serious transient voltage rise.
哈丽曼·合孜尔,樊艳芳.特高压直流故障对交流系统稳定性的影响分析[J].四川电力技术,2017,40(2):11-15. Haliman-Hezhier, Fan Yanfang. Analysis on Influence of UHVDC Failure on Stability of AC System[J]. SICHUAN ELECTRIC POWER TECHNOLOGY,2017,40(2):11-15.